36
Enclosure Options
Surge Protection
> UL 1449 3
rd
Edition Approved
> UL 1449 is required for installing surge
protection devices in cable enclosures
> SM Series has Status Monitoring failure
alarm via DSM3 cable harness
Surge Protection
Operating Voltage: 120V Models 240V Models 120/240V Models
Model Selection: Good Better Best Best Good Best Best Best
Series Model: LA-P+120 LA-P-120T LA-P-120S LA-P-120SM LA-P+240 LA-P-240S LA-P-240SM ISA 120/240
1
Part Number: 020-098-24 162-046-10 021-077-22 021-077-20 020-098-25 021-077-23 021-077-21 162-041-10
Outlet Type / Pass Thru:
/ No / Yes / Yes / Yes / No / Yes / Yes
Hardwired / NA
Status Monitor Harness: No No No Yes No No Yes No
Protection: L/N/G L/N/G L/N/G L/N/G L1/L2/G L1/L2/G L1/L2/G L/N/G
Operating Temperature:
-40 to 55°C /
-40 to 131°F
-40 to 55°C /
-40 to 131°F
-40 to 55°C /
-40 to 131°F
-40 to 55°C /
-40 to 131°F
-40 to 55°C /
-40 to 131°F
-40 to 55°C /
-40 to 131°F
-40 to 55°C /
-40 to 131°F
-40 to 55°C /
-40 to 131°F
LED Indicator: Yes Yes Yes Yes Yes Yes Yes Yes
Energy Absorption (Joules): 210 360 735 735 112 1170 1170 680
UL 1449 3
rd
Edition Specifications
Voltage Let Through
Protection Rating:
700Vp 660Vp
2
600Vp 600Vp 1200Vp 900Vp 900Vp 600Vp
2
/
900Vp
2
Nominal Discharge
Current Rating:
3kA 3kA 5kA 5kA 3kA 5kA 5kA 10kA
2
Maximum Continuous
Operating Voltage (MCOV):
150Vac 130Vac 175Vac 175Vac 320Vac 300Vac 300Vac 150Vac/300Vac
Notes:
1
The ISA surge protection devices are factory wired on the load side of the service entrance and are available for field replacement. These arrestors should be installed by a licensed electrician.
2
Pending UL 1449 3
rd
edition certification.
LA-P+
LA-P-120T
ISA-120/240
LA-P SM
COAX Protectors
Ideally suited to protect costly status-monitoring transponders, digital set top
boxes, cable modems and satellite receivers in the headend as well as high-end
HDTV sets from potentially damaging surges. The patented coaxial gas tube surge
protector is equipped with an integral fail-safe mechanism. Listed to UL 497, CSA
Listed Certified and Complies with 1999 National Electric Code.
Part Number Description
162-029-10: Female/Female connector configuration, “F” type connector
162-027-10: Male/Female connector configuration, “F” type connector
162-028-10:
Female/Female connector configuration, “F” type
connector with integral ground block
COAX Protectors
COAX Protector Specifications
Part Number: 162-029-10/162-027-10 162-028-10
RF Performance: DC – 1GHz 1GHz – 1.5GHz
Characteristic Impedance: 75Ohms 75Ohms
Insertion Loss (includes flatness): <0.1dB <0.2dB
Return Loss: >30dB >20dB
Protection
DC Breakdown @ 2000V/s: 150V to 300V
Impulse Breakdown @ 100V/µs: <450V
Insulation Resistance: >100 MegOhms
Surge Life
10A, 10/1000µs: >1500 Surges
100A, 10/1000µs: >100 Surges
1000A, 10/1000µs: >10 Surges
5000A, 8/20µs: >10 Surges
AC Life
5A, 1000Vac, 1s: >5 Operations
1A, 1000Vac, 1s: >60 Operations
Failshort
30A, 1000Vac: >15min
Operating Temperature: -40 to 65°C / -40 to 149°F