Cable Power Supplies
GMX
GMX
Models: GMX-915 GMX-915P
Electrical
Input Voltage (Vac): 120 240
Input Voltage Tolerance: ±30% @ 115V (80 to 150
v r m s ) ±30% @ 225V (158 to 292v r m s )
Line Return: ±25% ±25%
Nominal Input Current
1
: 13A 7A
Input Frequency: 60Hz 60Hz
Frequency Tolerance: ±3Hz ±3Hz
DC Voltage (Vdc): 36 36
Low DC Voltage Cutout: 1.75V/Cell 1.75V/Cell
Output Voltage (Vac): 63 / 87 (Field selectable) 63 / 87 (Field selectable)
Output Regulation, 87V Tap
2
: ±3% ±3%
Output Regulation, 63V Tap
2
: ±4% ±4%
Output Current: 15A 15A
Output Frequency Stability: 60Hz, ±1Hz (Inverter operation) 60Hz, ±1Hz (Inverter operation)
Waveform: Quasi-square wave Quasi-square wave
Battery Charger
Charge Current
3
: 10A 10A
Temperature Compensation: -5MV/Cell/°C (Programmable) -5MV/Cell/°C (Programmable)
Constant Current Operation: High Rate Charge to 90% Capacity High Rate Charge to 90% Capacity
Constant Voltage Operation: 2.4V/Cell (Typ. 7hrs) @ 25°C / 77°F 2.4V/Cell (Typ. 7hrs) @ 25°C / 77°F
Mechanical
Dimensions
H x W x D (in/mm):
7.8 x 18.3 x 11.4 / 198 x 465 x 290 7.8 x 18.3 x 11.4 / 198 x 465 x 290
Weight (lb/kg): 60 / 27.5 60 / 27.5
Front Panel Display (LCD): 2 x 20 Character LCD 2 x 20 Character LCD
Front Panel Indicators (LED): Output status and alarm Output status and alarm
Finish: Black, epoxy powdercoat Black, epoxy powdercoat
Environment
Operating Temperature: -40 to 55°C / -40 to 131°F -40 to 55°C / -40 to 131°F
Humidity: 0 to 95% non-condensing 0 to 95% non-condensing
Elevation: 0 to 3000m / 0 to 10000ft above sea level 0 to 3000m / 0 to 10000ft above sea level
Communication
Status Monitoring
4
: Optional DSM and ESM Optional DSM and ESM
Agency Compliance: UL 1778/CSA C22.2, No. 107.1 UL 1778/CSA C22.2, No. 107.1
Emissions: CISPR 22, Class A CISPR 22, Class A
Notes:
1
Batteries fully charged
2
Output regulation at nominal input frequency. Frequency variations will proportionally affect the output voltage (i.e., a 1% reduction in frequency will result in approximately a 1%
drop in output voltage)
3
Varies with input line voltage and output load
4
Status monitoring and embedded transponders are optional
> Line Interactive Ferro Technology (LIFT)
> Wide input voltage range of ±30%
> Compact packaging with light weight ferro
> Field programmable flash memory
> Integrated DOCSIS
®
Embedded Transponder
> Built-in battery circuit breaker
> IEC-style line cord
GMX
CableUPS
®
Power Supply
Przeglądanie stron 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 55 56

Komentarze do niniejszej Instrukcji

Brak uwag