041-028-B0-003, Rev. C
16
Fig. 3-7, Generator Grounding
3.0 Battery Cable Connections, continued
3.3 Grounding
Tools and Materials Needed:
#8AWG copper ground wire and clamps
Procedure:
1. Read and thoroughly understand the Engine Owner’s Manual before operating this
equipment.
2. Before starting the generator, follow all instructions outlined in the BEFORE OPERATION
section of the Engine Owner’s Manual.
3. Attach #8AWG copper grounding wire between the generator grounding lug and the
service entrance grounding bar, or directly to the utility grounding rod.
WARNING!
To prevent injury, the generator must share a common ground with the enclosure service
entrance.
Generator Grounding Lug